| Wall | Height mm | Setback mm | South boundary | North window opposite |
|---|
"North window opposite": the neighbour has a north-facing habitable room window within 3,000 mm of this boundary, within 3,000 mm either side of this wall.
Walls on or within 200 mm of the boundary, and carports within 1,000 mm. "Neighbour's wall" is the length of an abutting wall on their side, if longer.
One row per neighbour's habitable room window. The light court can include their land. Wall height is measured from the window's floor level if it's upstairs.
Estimate only: assumes the wall runs the full length of their open space and ignores existing shadows. Melbourne, 22 September, 9 am–3 pm. Prepare shadow diagrams to confirm.
Section check from 1,700 mm above floor level; confirm the 45° view cone and 9,000 mm radius on plan. Floor under 800 mm with a 1,800 mm fence is exempt.
One row per habitable room. A light court can't include the neighbour's land here. "Open ⅓": a verandah or carport open for ⅓ of its perimeter (carport: 2 or more sides open).
Side and rear fences only. If it's within 150 mm of the boundary, fill in its length and the boundary details too.
Same pathway as the Siting tab: change it here or there and both follow. Setbacks, height, walls, coverage, trees, fences, daylight, overlooking, overshadowing, permeability and neighbours' solar are on the Siting tab; everything else in Clause 54 or 55 is here.
Services width is checked against the frontage width on the Siting tab (20% max).
Ground level open space is checked on the Siting tab; the other types are checked here.
The south edge of the open space must be at least 2000 + 0.9 × the height of any wall on its north side.
Apartments: at least 40% of dwellings need a compliant breeze path.
Each needs: 850 mm clear entry and main bedroom doors; a 1200 mm clear path linking the entry, main bedroom, adaptable bathroom and living area; main bedroom access to the adaptable bathroom; and a bathroom to Design A or B in Table B3-12.
Per dwelling: 15 m² (1 bedroom), 26 m² (2–3), 34 m² (4+). At least 1700 mm wide, facing north, east or west, on the top two-thirds of a pitched roof, clear of obstructions by twice their height (unless they're to the south).
Enter the floor-to-floor rise and the tool suggests riser counts that work, with the going range for each. Constant risers and goings: no more than 5 mm between neighbours, 10 mm across a flight.
Needed where you can fall 1000 mm or more. "Climbable" = horizontal rails or ledges between 150 and 760 mm (not allowed where the fall is more than 4000 mm).
Bedrooms: floor 2000 mm or more above the ground and the opening lower than 1700 mm needs a restrictor or screen (125 mm sphere, 250 N). Other rooms: floor 4000 mm or more up needs an 865 mm barrier.
Position: on a flat ceiling at least 300 mm from the wall; on a sloping ceiling 500–1500 mm down from the apex; or on the wall 300–500 mm below the ceiling.
Fall to a floor waste: between 1:80 and 1:50. Shower walls waterproof to 1800 mm. Stepdown 25 mm. Unenclosed shower: waterstop 1500 mm from the rose.
Wall wrap class is the AS 4200.1 vapour permeance class printed on the product. Drained cavity: at least 12 mm deep, drained, with vents of 1000 mm² per metre at the bottom and top.
Make-up air for a room with no openable window: 14,000 mm² from the next room, e.g. a 20 mm undercut on a 700 mm door.
Find the category on VicPlan (Car Parking Requirement layer). If the land is in two categories, the higher one applies. Fractions round down. The "one dwelling on a lot" tick below also switches this off.
At 90° you can trade aisle for space width: 6400 aisle with 2600 spaces, 5800 with 2800, 5200 with 3000, 4800 with 3200. Disabled spaces follow AS/NZS 2890.6.
Victoria: NCC 2025 Vol Two Schedule 10 (VIC H2D6) takes Part 7.4 out as a deemed-to-satisfy route. Gutters and downpipes have to be designed to AS/NZS 3500.3. Use this tab as a first check only.
Eaves gutters handle the 5% AEP 5-minute storm; overflow measures handle the 1% storm. Each downpipe serves at most 12,000 mm of gutter and up to 70 m² of roof in the tables (more needs AS/NZS 3500.3). Overflow needed = 1% intensity × roof area ÷ 3600 (L/s), the same as Tables 7.4.4a–b. Eaves or verandahs wider than 450 mm with no lining (or a lining sloping away) don't need overflow measures.
Length is measured flat (on plan), not along the slope. The quick buttons fill in the gradient. Fill in the next section to check the grade change for scraping.
Applies to new Class 1a dwellings and the inside of Class 2 apartments (NCC Vol Two H8D2, Vol One G7). Victoria adopted NCC 2025 on 1 May 2026; jobs designed before then follow the NCC 2022 version, which is much the same. A Deemed-to-Satisfy check only.
Doors into habitable rooms and the laundry on the entry level, the attached garage on the access path, the toilet room and the shower room. Corridors leading to those doors.
Design Compliance Check Victoria is a free design aid. It checks a design against the Victorian Building Regulations, the Victoria Planning Provisions and the National Construction Code as summarised in this version. It is a guide only.
It is not a building permit, planning permit or professional assessment. Zone, overlay and parking schedules, council policies, Victorian variations and later amendments can change the requirements. Always confirm with the relevant building surveyor, council or other authority, and check the current legislation and standards.
The results depend on the information you enter. No responsibility is accepted for any loss arising from use of, or reliance on, this tool.
Contains information from the National Construction Code © Commonwealth of Australia and the States and Territories (ABCB), and the Victoria Planning Provisions and Building Regulations 2018 © State of Victoria, used under their licences. Version 20261126-0209.